192
192 Special check valves 1
192
Check valve with pump connection
  • Acceptable working temperature range (peaks): -20 (see suitable fluids)–110 °C
  • Working temperature range: 0 (no frost)–95 °C
  • Check valve opening pressure: 0,02 bar
  • Max working pressure: 16 bar
  • Suitable fluids: water for thermal systems, glycol solutions (max 30%), domestic water
  • Threaded connections: ISO 228-1
  • Product codes
  • Description
  • Documentation
Product codes
Item code Size Download the 3D file
192020000 G 1 1/2 RN - G 3/4 M - 80
192025000 G 1 1/2 RN - G 1 M - 80
Description
Barberi® check valves are monodirectional devices, allowing the backflow prevention of fluid under pressure. According to the model, they are normally used in domestic water installations, heating systems, central heating systems, heat generators (wall-mounted boilers, solid fuel generators, heat pumps), generic industrial and agricultural water systems. Sealing is permitted through forces exerted by a spring and by the fluid pressure against a gasket which guarantees the seal even at very low back pressures. Moreover, the force of the spring allows the valve to have a universal characteristics concerning the installation position. The peculiarity of this valve is the presence of the pump connection and drain device. This device is useful when filling the system (to rapidly discharge air) and draining (to allow the complete emptying of the system).
Documentation
Do you need help?