01G.DN50
01G.DN50 Distribution and regulating groups DN 50 1
01G.DN50
Direct group DN 50
  • Working temperature range: 5–90 °C
  • Max working pressure: 10 bar
  • Female connections: EN 10226-1
  • Male connections: ISO 228-1
  • Flanged connections: EN 1092 PN 16
  • Connection centre distance: 300 mm
  • Suitable fluids: water, glycol solutions (max 30%)
  • Temperature gauge scale: 0–120 °C
  • Product codes
  • Description
  • Documentation
  • Accessories
  • Alternative products
  • Spare parts
Product codes
Item code Size Manufacturer Pump Download the 3D file
01G05000X G 2 1/2 M - G 2 F 1 SenzaPompa WITHOUT PUMP
Description
Preassembled pump group for direct distribution or circulation. Allows the circulation of the thermal fluid, coming from the primary circuit, without performing any thermal regulation. It is used when the same flow temperature of the primary circuit is requested by the user in heating and cooling systems. The group is composed of flow/return shut-off valves, shut-off valve at the pump inlet, flow/return temperature gauges, anti-thermosiphon check valve, thermal insulation. The group is reversible (the flow line can be exchanged with the return line).
Documentation
Accessories
Alternative products
Spare parts