630.101.N
Thermostatic mixing valve for heating systems
- Temperature adjustment range: 25–50 °C
- Max working temperature: 90 °C
- Accuracy: ±2 °C
- Reference working conditions: hot T = 70 °C; cold T = 20 °C; hot and cold pressure = 0,7 bar
- Max static pressure (structural): 10 bar
- Flow coefficient: Kv 3,5
- Threaded connections: ISO 228-1; threaded connections EN 10226-1
- Suitable fluids: water for thermal systems, glycol solutions (max 50%)